                                                            Introduction to installation specification of current transformer
                                                            1 the installation of the current transformer must be firm. The exposed metal part of the transformer shell should be reliably connected.

                                                            2 The same set of current transformers should be installed in the same direction to ensure that the primary and secondary circuit currents of the current transformers are in the same direction and the nameplate can be easily observed.

                                                            3. The secondary side of the current transformer is not allowed to open circuit. When only one secondary circuit is used for the secondary double-turn transformer, the other secondary circuit should be reliably short-connected.

                                                            4 the low voltage current transformer can not be grounded on the two side. Because the conductors, watt-hour meters and transformers used in low-voltage metering devices have the same insulation level, the highest voltage they can withstand is basically the same; in addition, after the secondary windings are grounded, the insulation level of the primary circuit of the whole set of devices to the ground is reduced, which makes the watt-hour meters or transformers with insulation weaknesses easy to be damaged under high voltage (such as induced lightning strikes). Bad. It is better to reduce the damage caused by lightning damage to two sides.
                                                            Previous:Technical problems easy to appear in transformer test/ Next:How to use the current transformer correctly?
                                                            Products
                                                            Measuring current transformer
                                                            Metering current transformer
                                                            Protective current transformer
                                                            Leakage (residual) protection device
                                                            The zero sequence current transformer
                                                            Voltage transformer
                                                            Transmitter
                                                            Meter
                                                            common problem
                                                            How to use the current transformer correctly?
                                                            Introduction to installation specification of current transformer
                                                            Technical problems easy to appear in transformer test
                                                            Case
                                                            Contact Us

                                                            Address: No. 555 Shenze Road, Dongxi Industrial Zone, Jinhua, Zhejiang.
                                                            Zip code: 321017

                                                            Tel: 0579-82235395 82235362
                                                            Fax: 0579-82235388
                                                            Website: www.keyfirehose.com

                                                            E-mail: jhaokai@126.com

                                                            999zyz玖玖资源站免费_午夜精品一区二区香蕉片_天天综合影视网_青青草原超碰在线天堂